弯头别在工地现切
山东厂房、车库、写字楼做桥架,主线拉得再直,真到放电缆那天卡壳的常常不是直通,而是转弯那几截。现场梁柱躲不开、风管水管撞上了,工人图快拿砂轮切一段直通硬拼角度,看着装上了,隐患全埋在里面:切口毛刺划护套、镀锌层崩掉先锈、拼出来的弯度不够,电缆拐过去长期受侧压,绝缘慢慢就出问题。
Shandong factory buildings, garages, and office buildings make cable trays, and no matter how straight the main line is, the ones that get stuck on the day of cable laying are often not straight through, but in the corners. On site, the beams and columns could not be avoided, and the air ducts and water pipes collided. The workers tried to use a grinding wheel to cut a straight section through the hard splicing angle, but when they saw that it was installed, all the hidden dangers were buried inside: burrs on the cut, scratches on the protective sheath, rusting of the galvanized layer, insufficient bending of the splicing, and long-term lateral pressure on the cable turning over, gradually causing insulation problems.
为什么“现场弯”总出事
Why do 'on-site bends' always cause accidents
直通桥架是模具件,侧板折边、底板孔型都是按标准弧度走的;硬切硬拼,内侧半径往往小于电缆非常小允许弯曲半径(动力电缆一般 ≥12–15D,控制电缆 ≥6–10D)。
The straight cable tray is a mold component, and the side panel folding and bottom plate hole pattern are all designed according to standard curvature; Hard cutting and splicing, the inner radius is often smaller than the minimum allowable bending radius of the cable (power cables generally ≥ 12-15D, control cables ≥ 6-10D).

砂轮/无齿锯切完不打磨,内壁卷边像刀片,牵引电缆时“嗤”一声护套就破。
After cutting with a grinding wheel/toothless saw, it is not polished, and the inner wall is curled like a blade. When pulling the cable, the sheath will break with a "hiss" sound.
切口破坏镀锌层,不补富锌漆,山东冬天撒融雪剂、夏天地下室返潮,半年就从弯角开始锈穿。
The incision damages the galvanized layer without repairing the rich zinc paint. In Shandong, snow melting agents are sprayed in winter, and basement moisture returns in summer. Within six months, rust begins to penetrate from the corners.
拼焊弯通没有圆弧过渡,电缆在尖角处长期受压,比直段先老化。
There is no arc transition in the welded joint, and the cable is subjected to long-term compression at sharp corners, aging earlier than the straight section.
正确做法:弯通按实测尺寸定成品
Correct approach: Bend the finished product according to the measured size
放线阶段把每个转角实测三样——水平转角角度、垂直高差、梁底净空,直接报给厂家配成品水平弯、垂直弯、三通、变径。成品弯的内弧、盖板搭接、连接孔位都是冲出来的,螺栓一穿就位,不用现场比划。
During the laying out stage, three samples are measured for each corner - horizontal corner angle, vertical height difference, and beam bottom clearance, and directly reported to the manufacturer for finished products such as horizontal bending, vertical bending, tee joint, and variable diameter. The inner arc of the finished product bend, the overlap of the cover plate, and the connection hole positions are all punched out, and once the bolts are in place, there is no need for on-site marking.
现场实在躲不开要改一刀,记住三条底线:
If you can't escape from the scene, you need to make a change. Remember three bottom lines:
机械切割(无齿锯/台钻),禁用气割(烧穿镀锌和防火涂层);
Mechanical cutting (toothless saw/bench drill), gas cutting (burning through galvanized and fireproof coatings) is prohibited;
切口建议锉平去毛刺,露出基材处补刷富锌漆或防火涂料;
The incision must be filed flat and deburred, and the exposed substrate should be repainted with zinc rich paint or fireproof coating;
改完的弯角半径拿电缆样品比一下,过不去就别硬穿,回头补成品件。
Compare the modified bending radius with the cable sample. If it cannot pass through, do not force it on. We will repair the finished product later.
转弯处支吊架要“加一档”
The support and hanger at the turning point should be added by one level
规范里直通水平支架 1.5–3m、垂直 ≤2m,但弯头、三通、变径、端头 300–600mm 内建议各加一个支架。现场非常省事的就是弯头两边不设吊杆,结果重载一压,弯通下沉、连接片受扭,跨接线先松。
According to the specifications, a straight horizontal bracket of 1.5-3m and a vertical bracket of ≤ 2m must be added, but a bracket must be added within 300-600mm for elbows, tees, reducers, and ends. The most convenient thing on site is that there are no suspension rods on both sides of the bend, resulting in heavy load and sinking of the bend, twisting of the connecting piece, and loosening of the jumper wire.
顺手把跨接也盯了
I also watched the crossover casually
弯通段是非镀锌(喷塑/防火)桥架时,连接板两端跨接 ≥4mm² 黄绿铜软线,接触面刮漆见金属;镀锌桥架用带防松垫圈螺栓每端 ≥2 颗可免跨线,但弯头处建议也补一根,震动大容易松。
When the bent section is a non galvanized (spray painted/fireproof) bridge, the two ends of the connecting plate are bridged with ≥ 4mm ² yellow green copper flexible wire, and the contact surface is painted with metal visible; Galvanized cable trays can be equipped with at least 2 bolts with anti loosening washers at each end to avoid crossing the line, but it is recommended to add one bolt at the bend as it may loosen easily due to large vibrations.
验收就摸三下
Just touch three times for acceptance
手伸进弯通内弧摸一圈:无毛刺、无卷边、无焊瘤;
Insert your hand into the curved inner arc and touch it once: no burrs, no curled edges, no weld beads;
拿非常大那根电缆比弯:不蹭内弧、盖板能扣平;
Take the largest cable and compare bends: without rubbing against the inner arc, the cover plate can be fastened flat;
看切口补漆:弯角背面、底边有没有漏刷的白点。
Check if there are any white spots on the back and bottom of the corners that have been missed during the paint repair of the incision.
桥架直不直是面子,弯通做没做对是里子。山东项目赶工期,宁可多等两天成品弯通,也别让砂轮在工地“ creative ”出十个隐患点。
Whether the bridge is straight or not is face saving, and whether the bends are done correctly is the inside. The Shandong project is rushing to meet the deadline. It is better to wait for two more days for the finished product to bend, rather than letting the grinding wheel create ten hidden dangers on the construction site.
本文由山东电缆桥架友情奉献.更多有关的知识请点击:http://www.sdhangfeng.com我们将会对你提出的疑问进行详细的解答,欢迎你登录网站留言.
This article is a friendly contribution from Shandong Cable Bridge For more information, please click: http://www.sdhangfeng.com We will provide detailed answers to your questions. You are welcome to log in to our website and leave a message
下一篇:
相关文章 / Recommended news
托盘式电缆桥架选用指南是什么?
镀锌桥架接受着实际场景的严苛检验在哪?
网格桥架配件安装注意哪些事项?
电缆桥架防火性能是如何体现的?
电缆桥架内部电缆的布线方式有哪些?