填充率比单价更值钱

济南工地买桥架,采购单常只写“槽式200×100,热镀锌,每米报价”。等电缆放进去,盖板扣不上、转弯磨破皮、穿墙没封堵,返工成本比每米省的两毛钱高十倍。

When buying cable trays at construction sites in Jinan, the purchase order often only states "groove type 200 × 100, hot-dip galvanized, quoted per meter". When the cable is put in, the cover plate cannot be fastened, the turning is worn out, and the wall is not sealed, the rework cost is ten times higher than the two cents saved per meter.

结构先按电缆性质分,不按图片选:

The structure should be classified according to the nature of the cable first, without selecting according to the picture:

电缆桥架加厚角铁斜撑

弱电、监控、控制线:槽式,全封闭防尘防干扰;

Weak current, monitoring, and control lines: slot type, fully enclosed, dust-proof, and anti-interference;

动力+控制混敷、机房配电:托盘式,底板冲孔散热;

Power+control mixed installation, computer room power distribution: tray type, perforated bottom plate for heat dissipation;

厂房大截面主馈线:梯式,散热好、载荷大;

Factory building large section main feeder: ladder type, good heat dissipation, high load capacity;

消防回路:防火槽盒,要耐火检测报告,不是刷层防火漆。

Fire protection circuit: Fireproof trough box, fire resistance test report is required, not coated with fireproof paint.

板厚把“实厚”写进合同。宽度≤300mm底板≥1.2mm,300–600mm底板≥1.5mm,大跨距或>600mm加厚到1.5–2.0mm。底板、侧板、盖板分开标厚,弯通三通和直段同工艺同厚度,别直段厚、配件薄。

Write 'actual thickness' in the contract. Width ≤ 300mm, base plate ≥ 1.2mm, 300-600mm, base plate ≥ 1.5mm, with a large span or>600mm, thickened to 1.5-2.0mm. The base plate, side plate, and cover plate are separated by thickness, and the bent tee and straight section are of the same process and thickness, while the straight section is thicker and the accessories are thinner.

表面处理看环境:

Surface treatment depends on the environment:

室内干燥:电镀锌或喷塑;

Indoor drying: galvanizing or spray coating;

地下室、车库、普通厂房:热浸锌,锌层平均≥65μm,成品整体热浸锌,不拿冷镀冒充;

Basements, garages, and ordinary factories: hot-dip galvanized, with an average zinc layer of ≥ 65 μ m, and the finished product is hot-dip galvanized as a whole, without using cold plating as a substitute;

屋面、户外、化工区:热浸锌≥85μm或锌铝镁,强腐蚀上304/316L;

Roofing, outdoor, chemical area: hot-dip zinc ≥ 85 μ m or zinc aluminum magnesium, strong corrosion up to 304/316L;

消防通道:防火喷塑+防火隔板,配GB 8624燃烧性能和耐火检测报告。

Fire escape: fireproof spray coating+fireproof partition, equipped with GB 8624 combustion performance and fire resistance test report.

填充率死守红线:动力缆≤40%–50%,控制缆≤50%,留10%–25%扩容余量。桥架不是线槽仓库,塞满就失去散热通道,后期加线只能拆盖重做。

Fill rate firmly adheres to the red line: power cable ≤ 40% -50%, control cable ≤ 50%, leaving 10% -25% expansion margin. The cable tray is not a cable tray warehouse. If it is filled, it will lose the heat dissipation channel. In the later stage, adding cables can only be done by removing the cover and redoing.

安装现场五条硬杠:

Install five hard bars on site:

支架水平间距1.5–2m,转弯/三通/变形缝两端0.3–0.5m内加固定点;

The horizontal spacing between brackets is 1.5-2m, and fixed points are added within 0.3-0.5m at both ends of the turning/tee/deformation joint;

钢制直线超30m设伸缩节,过变形缝断开50mm加补偿;

Expansion joints shall be installed for steel straight lines exceeding 30m, and compensation shall be added if 50mm is disconnected through deformation joints;

转弯半径≥电缆外径10倍,不现场硬掰直角;

Turning radius ≥ 10 times the outer diameter of the cable, without on-site hard bending of right angles;

穿墙穿楼板用防火包+防火板双层封堵,厚度不低于墙厚,严禁水泥堵洞;

Fire resistant bags and double-layer fireproof boards are used to seal through walls and floors, with a thickness not less than the wall thickness. Cement blocking is strictly prohibited;

金属桥架全长不少于2处接PE干线,非镀锌段用≥4mm²软铜线跨接,起始端和终端都接。

The total length of the metal bridge shall be connected to PE main lines at no less than 2 points, and non galvanized sections shall be bridged with ≥ 4mm ² soft copper wires, with both the starting and ending ends connected.

到货验收四招:

Four tips for receiving and inspecting goods:

卡尺量实厚(扣掉涂层)、测厚仪查锌层、手摸内壁毛刺、样件称重对比封样。切割口补富锌漆,连接螺栓由内向外穿,螺母朝侧不伤电缆。

Measure the actual thickness with a caliper (remove the coating), check the zinc layer with a thickness gauge, touch the burrs on the inner wall with your hand, weigh and compare the sample before sealing. Add zinc rich paint to the cutting edge, thread the connecting bolts from the inside out, and ensure that the nut faces the side without damaging the cable.

桥架是电气系统的血管。前期只比每米单价,后期塞满电缆那天,盖板扣不上、防火验收打回、返工翻倍。

The bridge is the blood vessel of the electrical system. In the early stage, the price was only compared to the unit price per meter. However, on the day when the cables were packed in the later stage, the cover plate could not be fastened, the fire safety inspection was returned, and rework doubled.

 