桥架先定结构再挑材质
山东项目里桥架采购容易踩的第一个坑,是“按平米比价”。同尺寸铁皮槽子,结构形式不对,电缆散热和防火验收全卡。
The first pitfall that is easy to fall into when purchasing cable trays in Shandong projects is "comparing prices by square meter". The same size iron trough has an incorrect structural form, but the cable heat dissipation and fire prevention acceptance are fully qualified.
先分结构:
First, divide the structure:
槽式:全封闭带盖,适合弱电、控制、消防回路,防尘防干扰,但散热差,大截面动力主馈线别硬塞;

Slot type: fully enclosed with cover, suitable for weak current, control, and fire circuits, dustproof and anti-interference, but with poor heat dissipation. The large section power main feeder should be hard plugged;
托盘式:底板冲孔,动力+控制混敷主力,散热和承托平衡,厂房机房都用得着;
Tray type: perforated bottom plate, power+control mixed with main force, balanced heat dissipation and support, suitable for both factory and machine rooms;
梯式:横档开放,大截面电缆、主干馈线散热好,重载跨距大,但细控制线要加衬板;
Ladder style: The crossbar is open, and the large section cables and main feeders have good heat dissipation. The heavy-duty span is large, but the fine control lines need to be lined with plates;
防火槽盒:消防回路专用,要耐火检测报告,不是刷层防火漆就算数。
Fireproof trough box: dedicated for fire circuits, requires a fire resistance test report, not just a layer of fireproof paint.
材质和表面处理看环境:
Material and surface treatment depend on the environment:
室内干燥:电镀锌或喷塑够用;
Indoor drying: sufficient for galvanizing or spraying;
地下室、机房、一般车间:热浸锌,锌层≥65μm;
Basement, computer room, general workshop: hot-dip galvanizing, zinc layer ≥ 65 μ m;
户外、屋面、沿海:热浸锌≥85μm或锌铝镁,普通冷镀锌撑不住盐雾;
Outdoor, roof, coastal: hot-dip galvanizing ≥ 85 μ m or zinc aluminum magnesium, ordinary cold galvanizing cannot withstand salt spray;
化工腐蚀区:304/316L不锈钢或重防腐喷塑;
Chemical corrosion zone: 304/316L stainless steel or heavy-duty anti-corrosion spray coating;
消防通道:镀锌基体+防火涂层,配防火隔板和封堵。
Fire escape: galvanized substrate+fireproof coating, equipped with fireproof partition and sealing.
板厚按宽度和跨距双控:
Double control of plate thickness based on width and span:
≤300mm宽,底板≥1.0–1.2mm;
≤ 300mm width, base plate ≥ 1.0-1.2mm;
300–600mm,底板≥1.2–1.5mm;
300–600mm, Bottom plate ≥ 1.2-1.5mm;
600mm或大跨距,底板≥1.5–2.0mm;
600mm or large span, base plate ≥ 1.5-2.0mm;
合同里底板、侧板、盖板分开写实厚,不写“国标厚度”这种虚词。
In the contract, the bottom plate, side plate, and cover plate should be separated and made thick, without using the term 'national standard thickness'.
安装现场五条红线:
Five red lines at the installation site:
支架水平间距≤1.5–2.0m,转弯/三通/接头两端0.3–0.5m内加支架;
The horizontal spacing between brackets should be ≤ 1.5-2.0m, and brackets should be added within 0.3-0.5m at both ends of bends/tees/joints;
钢制直线超30m设伸缩节,跨变形缝加补偿;
Expansion joints shall be installed for steel straight lines exceeding 30m, and compensation shall be added for cross deformation joints;
转弯半径≥电缆外径10倍(控制电缆6–10倍),不用现场硬掰直角;
Turning radius ≥ 10 times the outer diameter of the cable (6-10 times the control cable), no need to forcefully bend right angles on site;
穿墙穿楼板用防火包+防火泥+隔板封堵,留洞不封等于消防隐患;
Using fireproof bags, fireproof mud, and partitions to seal through walls and floors, leaving holes unsealed is equivalent to a fire hazard;
金属桥架全长至少2处接PE干线,镀锌桥架连接片两端防松螺栓保导通,非镀锌段跨接≥4mm²软铜线。
At least 2 locations along the entire length of the metal bridge shall be connected to the PE main line. Anti loosening bolts shall be used at both ends of the galvanized bridge connecting piece to ensure conductivity. Non galvanized sections shall be bridged with ≥ 4mm ² soft copper wire.
进场验收四招:
Four methods for on-site acceptance:
卡尺量实厚、测厚仪查锌层、游标卡边看毛刺、样件称重对比封样。切割切口补富锌漆,连接螺栓螺母朝外不伤电缆。
Measure the actual thickness with a caliper, check the zinc layer with a thickness gauge, check for burrs with a vernier caliper, weigh and compare the sample before sealing. Cut the incision and apply rich zinc paint, with connecting bolts and nuts facing outward without damaging the cable.
桥架不是“铁皮槽子挂上去”,是把“结构—材质—板厚—跨距—接地—封堵”焊成电气系统的一根血管。前期只比每米单价,后期塞满电缆那天,盖板扣不上、防火验收打回、返工成本翻倍。
The bridge frame is not hung on a metal groove, but welded as a blood vessel of the electrical system by "structure material plate thickness span grounding sealing". In the early stage, the price was only compared to the unit price per meter. However, on the day when the cables were packed in the later stage, the cover plate could not be fastened, the fire safety inspection was returned, and the rework cost doubled.