网站公告-NOTICE
联系我们
济南航丰实业有限公司

电话:15168870138
联系人:庞经理

网址:http://www.sdhangfeng.com  

厂址: 德州市禹城市莒镇产业园26栋

经销商地址:天桥区建华五金市场东区5-1  

鲁ICP备09095923号-1

新闻资讯

当前位置:首页 / 新闻资讯

支架间距别死套表

桥架装得再直,电缆一放上去中间塌腰,多半是支架间距没按实际荷载算。现场班组爱背“水平 2 米一个、垂直 2 米一个”,这话只适用于轻载槽式桥架,梯式、大跨距、满载电缆的场景一套就出事。

No matter how straight the cable tray is installed, if the cable collapses in the middle when it is placed, it is likely that the spacing between the supports is not calculated according to the actual load. The on-site team loves to carry "2-meter-long horizontal and 2-meter-long vertical cables", which only applies to light load trough type cable trays, ladder type, large-span, and fully loaded cable scenarios.

梯式电缆桥架

先分结构看基准:

First, look at the structure and benchmark:

槽式/托盘式(常规电缆):水平支架 1.5–2 m,垂直 ≤2 m;

Slot/tray type (conventional cable): horizontal bracket 1.5-2 m, vertical ≤ 2 m;

梯式(动力电缆多、自重沉):水平 1.5 m​ 起步,重载段压到 1.2 m;

Ladder type (with multiple power cables and heavy weight): starting from 1.5 meters horizontally, the heavy load section is compressed to 1.2 meters;

大跨距桥架(桁架或加厚梯式):可以放到 3–6 m,但得看厂家给的跨距荷载曲线,不是自己拍脑袋拉长;

Large span bridge frame (truss or thickened ladder type): can be placed at 3-6 meters, but it depends on the span load curve provided by the manufacturer, not self stretching;

弯通、三通、变径、端部 0.3–0.5 m 内必加独立支架,别指望连接板扛扭力。

Bends, tees, reducers, and independent brackets must be added within 0.3-0.5 meters of the end. Do not expect the connecting plate to withstand torque.

比间距更容易翻车的是荷载校核。桥架自重 + 电缆满配重量(查电缆样本 kg/m × 根数)÷ 支架间距 = 单支点受力。比如 200×100 梯式满放 4 根 3×95+1×50 动力缆,电缆就 60 多 kg/米,2 m 间距单架吃 120 kg 以上,普通角钢横担直接弯。这种情况要么缩到 1.2 m,要么换槽钢横担+斜撑。

Load verification is more prone to overturning than spacing. The self weight of the bridge+the full weight of the cable (check the cable sample in kg/m x number of cables) ÷ the spacing between the supports=the force on a single support point. For example, if a 200 × 100 ladder is fully loaded with 4 3 × 95+1 × 50 power cables, the cables will weigh over 60 kg/meter, and a single rack with a spacing of 2 meters will weigh over 120 kg. Ordinary angle steel crossarms can be bent directly. In this case, either shrink to 1.2 m or change the channel steel cross arm+slant support.

山东这边还有两个本地坑:

There are two local pitfalls in Shandong:

温差:冬天冷缩、夏天热胀,长直段支架别全焊死,中间留几个滑动支座,不然接缝张口、螺栓受剪;

Temperature difference: Cold shrinkage in winter and hot expansion in summer. The long straight section bracket should not be completely welded, and a few sliding supports should be left in the middle to prevent joint opening and bolt shear;

穿墙/楼板洞口:两侧 300 mm 内各加一个支架,别让洞口悬臂受力,防火封堵压完才不会把桥架压歪。

Wall/floor opening: Add a bracket within 300mm on both sides to prevent the opening from being cantilevered and subjected to force. Only after the fireproof sealing is completed can the bridge be prevented from being tilted.

顺手记一句:支架本身也得接地连续,金属横担和桥架本体用跨接线或防松螺栓连通,全长不少于 2 处接 PE 干线——这条和间距一样,验收时一起查。

By the way, the bracket itself must also be grounded continuously. The metal crossbar and the bridge body should be connected with jumper wires or anti loosening bolts, and the total length should not be less than 2 PE main lines - this one has the same spacing and should be checked together during acceptance.

桥架这东西,板厚决定耐不耐造,支架决定塌不塌腰。间距表只是起点,按电缆实重反算一遍,比背规范数字稳得多。

The thickness of the bridge determines its durability, while the support determines whether it will collapse or not. The spacing table is just the starting point. Calculating it backwards based on the actual weight of the cable is much more stable than memorizing the standard numbers.

 
qq
售前咨询热线
15168870138
售后咨询热线
13465410318