桥架里的“热应力”

山东四季温差大,桥架装完头一年非常容易出现一种怪现象:春天还横平竖直,入冬后接缝张开、螺栓受拉,夏天又顶得支架微歪。这不是桥架质量差,是热胀冷缩在“用力”。

Shandong has a large temperature difference throughout the four seasons, and in the first year after the installation of the bridge, a strange phenomenon is most likely to occur: in spring, the bridge is still horizontal and vertical, in winter, the joints open and the bolts are pulled, and in summer, the support is slightly tilted. This is not due to poor quality of the bridge frame, but rather due to thermal expansion and contraction under pressure.

钢制桥架线膨胀系数约 12×10⁻⁶/℃。一段 30 米直线桥架,冬夏温差 50℃,理论伸缩量约 18mm。看着不大,但被支架死死锁住,力会传到连接板和锚栓上,时间久了接口错台、镀锌层崩裂。

The expansion coefficient of the steel bridge frame is about 12 × 10 ⁻⁶/℃. A 30 meter straight cable tray with a temperature difference of 50 ℃ between winter and summer, with a theoretical expansion and contraction of about 18mm. It looks small, but it is tightly locked by the bracket, and the force will be transmitted to the connecting plate and anchor bolt. Over time, the interface will be misaligned and the galvanized layer will crack.

灰色喷塑电缆桥架

所以规范里写得很清楚:钢制直线超 30 米要设伸缩节,铝合/玻璃钢超 15 米就要设。跨建筑变形缝、沉降缝建议加补偿装置,留 20–50mm 余量,不能拿普通连接板硬顶。

So the specifications are very clear: expansion joints should be installed for steel straight lines exceeding 30 meters, and expansion joints should be installed for aluminum/fiberglass over 15 meters. Compensation devices must be added to cross building deformation joints and settlement joints, leaving a margin of 20-50mm, and ordinary connecting plates cannot be used for hardtop.

伸缩节装了不算完,细节常错:

The installation of the expansion joint is not complete, and the details are often wrong:

伸缩节两侧 600mm 内各补一个支架,不然伸缩段悬空,往复位移把螺栓晃松;

Add a bracket within 600mm on each side of the expansion joint, otherwise the expansion section will be suspended and the reciprocating displacement will loosen the bolts;

非镀锌桥架在伸缩处仍要软铜绞线跨接(≥16mm²),不能因为“能活动”就断开接地;

Non galvanized cable trays still need to be bridged with soft copper stranded wires (≥ 16mm ²) at the expansion point, and the grounding should not be disconnected just because they are "movable";

伸缩节本身别锁死,调节螺栓留活动余量,否则失去补偿意义。

Do not lock the expansion joint itself, leave enough room for movement when adjusting the bolts, otherwise it will lose its compensating significance.

和热力管道同廊时更要注意。桥架和热水管、蒸汽管平行,没留间距也没隔热,电缆长期受热,绝缘老化加快。规范上桥架与热力管净距有硬性要求,现场却常为了“省空间”贴着走,后期载流量偷偷下降。

Pay more attention when sharing the same corridor as the thermal pipeline. The cable tray is parallel to the hot water pipe and steam pipe, without any spacing or insulation. The cable is heated for a long time, and the insulation aging accelerates. There are strict requirements for the clear distance between the bridge frame and the heat pipe in the standard, but on site, they often stick to it in order to "save space", and the later current carrying capacity secretly decreases.

验收时别只看“直不直”。拿塞尺查伸缩节间隙,看支架有无被拉歪,摸连接板有无异常应力裂纹。运行半年后复检一次,比出问题再停电能省很多事。

Don't just look at whether it's straight or not during acceptance. Use a ruler to check the gap between the expansion joint, check if the bracket is pulled off, and touch the connecting plate for any abnormal stress cracks. Recheck after half a year of operation, which can save a lot of trouble compared to cutting off power when problems arise.

桥架系统里,刚性和柔性要共存:平时靠支架定形,温差来了靠伸缩节泄力。只强调“装得牢”,不考虑“留得动”,系统反而不稳。

In the bridge system, rigidity and flexibility need to coexist: usually relying on brackets to shape, and relying on expansion joints to release force when temperature differences occur. Emphasizing only 'being securely installed' without considering 'being able to move', the system is actually unstable.

 