济南电缆桥架: 桥架间距应该如何设置?
电缆桥架水平安装时,支吊架之间距离适合在1.5米~2米,在转弯处的支吊架间距应为0.3米~0.6米,垂直安装电缆桥架时,支吊架间的距离不应该超过2米。下面由济南航丰实业的小编给大家介绍一下安装电缆桥架间距要求的相关内容。
When installing cable trays horizontally, the distance between supports and hangers should be suitable between 1.5 to 2 meters. The distance between supports and hangers at turns should be between 0.3 to 0.6 meters. When installing cable trays vertically, the distance between supports and hangers should not exceed 2 meters. Below, the editor from Jinan Hangfeng Industry will introduce the relevant content on the spacing requirements for installing cable trays.
电缆桥架与一般工艺管道平行铺设时,敷设间隔少400毫米,与工艺管道交叉敷设时,安装间距小为300毫米,电缆桥架与腐蚀气体管道的平行间距少为500毫米,交叉间距小为500毫米。电缆桥架水平安装时,应该按照载荷规范选择支、吊架间距,距离不应该大于2米。电缆桥架支、吊架的间距也要参考其产品性能参数说明来设置。
When the cable tray is laid parallel to the general process pipeline, the laying interval should be at least 400 millimeters. When cross laid with the process pipeline, the installation interval should be at least 300 millimeters. The parallel spacing between the cable tray and the corrosive gas pipeline should be at least 500 millimeters, and the cross spacing should be at least 500 millimeters. When installing cable trays horizontally, the spacing between supports and hangers should be selected according to the load specifications, and the optimal distance should not exceed 2 meters. The spacing between cable tray supports and hangers should also be set according to the product performance parameter specifications.

单层电缆桥架安装时,配套支吊架的间距不应该大于2米,电缆桥架多层同时敷设时,支吊架之间的距离应该根据载荷进行具体计算。电缆桥架与无保温的热力管道水平敷设时,平行间距少为1米,交叉铺设时的小间距应为0.5米,电缆桥架与有保温措施的热力管道交叉敷设时距离小为300毫米,水平铺设时距离少为500毫米。
When installing single-layer cable trays, the spacing between supporting brackets should not exceed 2 meters. When laying multiple layers of cable trays simultaneously, the distance between brackets should be calculated specifically based on the load. When cable trays are horizontally laid with uninsulated thermal pipelines, the parallel spacing should be at least 1 meter, and the minimum spacing when cross laid should be 0.5 meters. When cable trays are cross laid with insulated thermal pipelines, the minimum distance is 300 millimeters, and when horizontally laid, the distance is at least 500 millimeters.
本文由 济南电缆桥架 友情奉献。更多有关的知识请点击: http://www.sdhangfeng.com 真诚的态度,为您提供为的服务。更多有关的知识我们将会陆续向大家奉献,敬请期待。
This article is dedicated to the friendship of Jinan cable tray. For more information, please click on: http://www.sdhangfeng.com Sincere attitude, providing you with comprehensive service. We will gradually contribute more relevant knowledge to everyone, please stay tuned.
下一篇:山东电缆桥架:电缆桥架与支架如何连接?
相关文章 / Recommended news
- 济南电缆桥架选购指南:热镀锌与热浸锌一字之差,应用场景与天壤之别
- 山东工程人必看!桥架安装验收7大硬标准,少一项都要返工,附详细数据
- 济南厂房福音!大跨距桥架破解3大痛点,加强筋加,安装省一半钱
- 山东工程人警惕!桥架敷线踩这坑必返工,监理当场叫停,国标早有明确规定
- 济南人避坑!桥架≠线槽,90%工程人都搞混,一字之差差千里
- 避坑指南!山东电缆桥架规格别瞎选,偏大浪费偏小隐患大,国标早就定好了
- 济南人必看!铝合金电缆桥架选对厚度,耐用又省心,90%的人选错踩坑
- 山东人必看!电缆桥架不是“铁架子”,藏着建筑用电的密码,90%的人都不懂
- 800kg/m抗压!济南电缆桥架,破解3大工程痛点,工期省30%
- 3种类型+98%散热!山东电缆桥架,选对不踩坑,布线效率翻倍
阳极氧化铝合金桥架
托盘式电缆桥架
梯式电缆桥架
梯式不锈钢电缆桥架
深灰色金属防火电缆桥架